PLC Analog Scaling Calculator

Scale raw PLC analog values such as 0–27648 to engineering units—quickly, transparently, and directly in your browser.

PLC & AutomationAnalog inputPLC scalingEngineering units4–20 mA

Calculator

On a Siemens input configured for 4–20 mA, 4 mA maps to raw 0 and 20 mA maps to raw 27648.

bar
bar

For example bar, °C, l/min, or %.

Scaled value: 5 bar

Result

Scaled value

5 bar

Normalized position

50 %

Range status

Within nominal range

Input value

13,824

Linear formula used

y = y₀ + (x − x₀) × (y₁ − y₀) / (x₁ − x₀)

The range status evaluates the configured scaling endpoints. Hardware diagnostics such as wire break, underflow, and overflow are module-specific and must be evaluated separately.

Formula and calculation method

This calculator maps a raw value linearly onto any engineering range. The inverse direction determines the PLC count required for a physical value.

Normalized: t = (raw − raw min) / (raw max − raw min)

Scaled: engineering = eng min + t × (eng max − eng min)

Inverse: raw = raw min + (engineering − eng min) × (raw max − raw min) / (eng max − eng min)

Assumptions and limitations

  • For correctly configured Siemens current channels, the nominal range is 0…27648; with a configured 4–20 mA signal, 4 mA corresponds to raw 0 and 20 mA to raw 27648.
  • Bipolar Siemens voltage ranges such as ±10 V typically use −27648…27648.
  • Values outside the nominal range are extrapolated and marked as under/over-range by default. Limiting occurs only when Clamp is explicitly selected.
  • Custom 0%/100% endpoints may descend for a generic inverted characteristic. To reproduce Siemens NORM_X or SCALE_X exactly, follow their MIN < MAX requirement.
  • Diagnostic and overrange values depend on the exact module and configuration; its hardware manual remains authoritative.

Technical sources