Industrial integration guide
OPC UA to MQTT Gateway
Expose selected OPC UA values as structured MQTT topics without giving the broker direct access to the control network. Sync Connect reads the server, applies the route configuration and publishes only the data the IT side needs.
Architecture.
Deploy Sync Connect at the OT/IT boundary. It opens a client connection to the OPC UA server and a separate connection to the MQTT broker, so neither endpoint needs to reach through the other network zone.
OPC UA server
Sync Connect integration layer
MQTT broker
When this route fits.
Publish PLC and SCADA values to an edge or enterprise MQTT broker.
Feed condition monitoring, dashboards or event-driven applications.
Replace one-off OPC UA polling scripts with version-controlled routes.
Configuration pattern.
This minimal pattern uses the same provider, connector and route model as the production configuration. Replace the endpoint, broker and node identifiers with values from your environment.
resources:
line-metrics:
temperature: ns=4;i=1
pressure: ns=4;i=2
providers:
line-opc:
driver: opcua
config:
endpoint: opc.tcp://192.168.10.20:4840
connectors:
production-mqtt:
driver: mqtt
config:
broker: 192.168.20.15
routes:
factory/line-1/metrics:
mode: read
provider: line-opc
resource: line-metricsNode IDs, certificate policy and credentials are project-specific and must be validated against the OPC UA server and broker before commissioning.
Technical fit.
- Source protocol
- OPC UA over opc.tcp
- Target protocol
- MQTT
- Data direction
- Read routes; controlled write-back where required
- Deployment
- Linux or Windows, ARM or x86
Security and network.
- Allow the gateway to reach the OPC UA endpoint; do not expose the PLC network to the broker.
- Use certificate trust lists and an OPC UA account limited to the required nodes.
- Use authenticated, encrypted MQTT and restrict the client to its assigned topic prefix.
- Synchronize time across the server, gateway and broker so event timestamps remain comparable.
Failure and recovery behaviour.
OPC UA unavailable
Treat loss of source quality as a separate state from a valid zero value. Test reconnect timing and the quality signal consumed by downstream systems.
Broker unavailable
Define the permitted buffer window and recovery rate during acceptance. Size it from message volume and the maximum tolerated outage.
Write-back
Keep routes read-only unless a documented setpoint use case exists. Test authorization, value ranges and the safe state independently.
Limitations and better alternatives.
- The gateway does not repair an inconsistent OPC UA information model or missing source timestamps.
- High-frequency waveform data may require aggregation or a purpose-built transport rather than one MQTT message per sample.
- A broker topic model still needs ownership, naming and retention rules; protocol conversion alone does not provide data governance.